哪位有C#与三菱PLC通讯的源码,最好有实例

2025-03-15 01:05:40
推荐回答(5个)
回答1:

提供一个C#与FX5U以太网通讯的代码:


using System.Collections.Generic;
using System;
using System.Linq;
using System.Drawing;
using System.Diagnostics;
using System.Data;
using System.Xml.Linq;
using Microsoft.VisualBasic;
using System.Collections;
using System.Windows.Forms;


using System.Net;
using System.Runtime.InteropServices;

namespace TCP_CLIENT
{
public partial class Form1
{
public Form1()
{
InitializeComponent();


if (defaultInstance == null)
defaultInstance = this;
}

#region Default Instance

private static Form1 defaultInstance;


public static Form1 Default
{
get
{
if (defaultInstance == null)
{
defaultInstance = new Form1();
defaultInstance.FormClosed += new FormClosedEventHandler(defaultInstance_FormClosed);
}

return defaultInstance;
}
set
{
defaultInstance = value;
}
}

static void defaultInstance_FormClosed(object sender, FormClosedEventArgs e)
{
defaultInstance = null;
}

#endregion


EntFxPlc.PlcClient PLC = new EntFxPlc.PlcClient();
bool EntLink;
long ScanCount;
short ScanRet;
        Int32 PlcHand;

[DllImport("winmm.dll", ExactSpelling=true, CharSet=CharSet.Ansi, SetLastError=true)]
public static extern UInt32 timeGetTime();

public void Form1_Load(System.Object sender, System.EventArgs e)
{
this.CenterToScreen();
cmbReadMry.Items.Clear();
cmbReadMry.Items.Add("X");
cmbReadMry.Items.Add("Y");
cmbReadMry.Items.Add("M");
cmbReadMry.Items.Add("D");
cmbWriteMry.Items.Clear();
cmbWriteMry.Items.Add("X");
cmbWriteMry.Items.Add("Y");
cmbWriteMry.Items.Add("M");
cmbWriteMry.Items.Add("D");
cmbBitMry.Items.Clear();
cmbBitMry.Items.Add("X");
cmbBitMry.Items.Add("Y");
cmbBitMry.Items.Add("M");
cmbReadType.Items.Clear();
cmbReadType.Items.Add("INT16");
cmbReadType.Items.Add("UINT16");
cmbReadType.Items.Add("DINT32");
cmbReadType.Items.Add("HEX32");
cmbReadType.Items.Add("REAL32");
cmbReadType.Items.Add("BIN16");
cmbWriteType.Items.Clear();
cmbWriteType.Items.Add("INT16");
cmbWriteType.Items.Add("UINT16");
cmbWriteType.Items.Add("DINT32");
cmbWriteType.Items.Add("HEX32");
cmbWriteType.Items.Add("REAL32");
cmbWriteType.Items.Add("BIN16");
cmbReadMry.SelectedIndex = 3;
cmbWriteMry.SelectedIndex = 3;
cmbBitMry.SelectedIndex = 2;
cmbReadType.SelectedIndex = 0;
cmbWriteType.SelectedIndex = 0;
lstRead.Items.Clear();
txtWrite.Text = "";
            cmbCmdType.SelectedIndex = 0;
}


public void butLink_Click(System.Object sender, System.EventArgs e)
{
short re = 0;
string restr = "";
            re = PLC.EntLink(txtLocalIP.Text.Trim(), Convert.ToUInt16(txtLocalPort.Text), txtRemoteIP.Text.Trim(), (Convert.ToUInt16(txtRemotePort.Text)),  "DEMO", ref PlcHand,Convert .ToUInt16 (1000),Convert .ToBoolean (cmbCmdType .SelectedIndex ));
txtReLink.Text = re.ToString();
if (re == 0)
{
EntLink = true;
MessageBox.Show("PLC联接成功!");
}
else
{
EntLink = false;
MessageBox.Show("PLC联接失败: " + restr);
}
}

public void butClose_Click(System.Object sender, System.EventArgs e)
{
short re = 0;
            EntLink = false;
            re = PLC.DeLink(PlcHand);
txtReClose.Text = re.ToString();
}

public void butRead_Click(System.Object sender, System.EventArgs e)
{
short i = 0;
object[] RD = null;
RD = new object[Convert.ToUInt16(txtReadCnt.Text)];
if (!EntLink)
{
MessageBox.Show("还未与PLC建立联接!");
return;
}
int var1 = cmbReadType.SelectedIndex + 1;
            EntFxPlc.PlcClient.DataType typ = (EntFxPlc .PlcClient.DataType)var1;
switch (cmbReadMry.SelectedIndex)
{
case 0:
                    ScanRet = PLC.CmdRead(PlcHand,EntFxPlc.PlcClient.PlcMemory.DI, typ,    Convert.ToUInt16(txtReadAdd.Text), Convert.ToUInt16(txtReadCnt.Text), ref RD);
break;
case 1:
                    ScanRet = PLC.CmdRead(PlcHand, EntFxPlc.PlcClient.PlcMemory.DQ, typ,   Convert.ToUInt16(txtReadAdd.Text), Convert.ToUInt16(txtReadCnt.Text), ref RD);
break;
case 2:
                    ScanRet = PLC.CmdRead(PlcHand, EntFxPlc.PlcClient.PlcMemory.MR, typ,   Convert.ToUInt16(txtReadAdd.Text), Convert.ToUInt16(txtReadCnt.Text), ref RD);
break;
case 3:
                    ScanRet = PLC.CmdRead(PlcHand, EntFxPlc.PlcClient.PlcMemory.DR, typ,   Convert.ToUInt16(txtReadAdd.Text), Convert.ToUInt16(txtReadCnt.Text), ref RD);
break;
}
txtReRead.Text = ScanRet.ToString();
lstRead.Items.Clear();
for (i = 0; i <= (RD.Length - 1); i++)
{
if (!(RD[i] == null))
{
lstRead.Items.Add(RD[i]);
}
else
{
lstRead.Items.Add("0");
}
}

}


public void butWrite_Click(System.Object sender, System.EventArgs e)
{
short i = 0;
string[] temp = null;
object[] WD = null;
if (!EntLink)
{
MessageBox.Show("还未与PLC建立联接!");
return;
}
WD = new object[Convert.ToUInt16(txtWriteCnt.Text)];
temp = txtWrite.Text.Split('\n');
for (i = 0; i <= (WD.Length - 1); i++)
{
if (i > (temp.Length - 1))
{
WD[i] = 0;
}
else
{
WD[i] = temp[i].Trim();
}
}
int var1 = cmbWriteType.SelectedIndex + 1;
            EntFxPlc.PlcClient.DataType typ = (EntFxPlc.PlcClient.DataType)var1;
switch (cmbWriteMry.SelectedIndex)
{
case 0:
                    ScanRet = PLC.CmdWrite(PlcHand, EntFxPlc.PlcClient.PlcMemory.DI, typ,   Convert.ToUInt16(txtWriteAdd.Text), Convert.ToUInt16(txtWriteCnt.Text), ref WD);
break;
case 1:
                    ScanRet = PLC.CmdWrite(PlcHand, EntFxPlc.PlcClient.PlcMemory.DQ, typ,   Convert.ToUInt16(txtWriteAdd.Text), Convert.ToUInt16(txtWriteCnt.Text), ref WD);
break;
case 2:
                    ScanRet = PLC.CmdWrite(PlcHand, EntFxPlc.PlcClient.PlcMemory.MR, typ,   Convert.ToUInt16(txtWriteAdd.Text), Convert.ToUInt16(txtWriteCnt.Text), ref WD);
break;
case 3:
                    ScanRet = PLC.CmdWrite(PlcHand, EntFxPlc.PlcClient.PlcMemory.DR, typ,   Convert.ToUInt16(txtWriteAdd.Text), Convert.ToUInt16(txtWriteCnt.Text), ref WD);
break;
}
txtReWrite.Text = ScanRet.ToString();
}

public void butScan_Click(System.Object sender, System.EventArgs e)
{
if (!EntLink)
{
MessageBox.Show("还未与PLC建立联接!");
return;
}
if (butScan.Text == "Cycle R/W")
{
ScanCount = 0;
Timer1.Enabled = true;
butScan.Text = "Stop R/W";
}
else
{
Timer1.Enabled = false;
butScan.Text = "Cycle R/W";
}
}

public void Timer1_Tick(System.Object sender, System.EventArgs e)
{
            Timer1.Enabled = false;
            int tim = System.Convert.ToInt32(timeGetTime());
            if (!EntLink)
            {
                MessageBox.Show("还未与PLC建立联接!");
                return;
            }
            //
            butRead_Click(null, null);
            butWrite_Click(null, null);

            //
            if ((Convert.ToInt32(txtReRead.Text) < 0) || (Convert.ToInt32(txtReWrite.Text) < 0))
            {
                butScan.Text = "Cycle R/W";
                return;
            }
            else
            {
                ScanCount++;
                txtScanCnt.Text = ScanCount.ToString();
                txtScanPrd.Text = (System.Convert.ToInt32(timeGetTime()) - tim).ToString() + "ms";
            }
            Timer1.Enabled = true;
}


public void butBitTest_Click(System.Object sender, System.EventArgs e)
{
if (!EntLink)
{
MessageBox.Show("还未与PLC建立联接!");
return;
}
bool rd = false;
short re = 0;
switch (cmbBitMry.SelectedIndex)
{
case 0:
                    re = PLC.Bit_Test(PlcHand, EntFxPlc.PlcClient.PlcMemory.DI,   Convert.ToUInt16(txtBitAdd.Text), ref rd);
break;
case 1:
                    re = PLC.Bit_Test(PlcHand, EntFxPlc.PlcClient.PlcMemory.DQ,   Convert.ToUInt16(txtBitAdd.Text), ref rd);
break;
case 2:
                    re = PLC.Bit_Test(PlcHand, EntFxPlc.PlcClient.PlcMemory.MR,   Convert.ToUInt16(txtBitAdd.Text), ref rd);
break;
}
txtBitTest.Text = rd.ToString();
txtReBit.Text = re.ToString();
}

public void butBitSet_Click(System.Object sender, System.EventArgs e)
{
if (!EntLink)
{
MessageBox.Show("还未与PLC建立联接!");
return;
}
short re = 0;
switch (cmbBitMry.SelectedIndex)
{
case 0:
                    re = PLC.Bit_Set(PlcHand, EntFxPlc.PlcClient.PlcMemory.DI,   Convert.ToUInt16(txtBitAdd.Text));
break;
case 1:
                    re = PLC.Bit_Set(PlcHand, EntFxPlc.PlcClient.PlcMemory.DQ,   Convert.ToUInt16(txtBitAdd.Text));
break;
case 2:
                    re = PLC.Bit_Set(PlcHand, EntFxPlc.PlcClient.PlcMemory.MR,   Convert.ToUInt16(txtBitAdd.Text));
break;
}
txtReBit.Text = re.ToString();
}

public void butBitRst_Click(System.Object sender, System.EventArgs e)
{
if (!EntLink)
{
MessageBox.Show("还未与PLC建立联接!");
return;
}
short re = 0;
switch (cmbBitMry.SelectedIndex)
{
case 0:
                    re = PLC.Bit_Reset(PlcHand, EntFxPlc.PlcClient.PlcMemory.DI,   Convert.ToUInt16(txtBitAdd.Text));
break;
case 1:
                    re = PLC.Bit_Reset(PlcHand, EntFxPlc.PlcClient.PlcMemory.DQ,   Convert.ToUInt16(txtBitAdd.Text));
break;
case 2:
                    re = PLC.Bit_Reset(PlcHand, EntFxPlc.PlcClient.PlcMemory.MR,   Convert.ToUInt16(txtBitAdd.Text));
break;
}
txtReBit.Text = re.ToString();
}


}

}

回答2:

百度C#与OPC通讯,照着做就可以了!这个需要自动化方面的人配合,帮你把PLC 的tag点给你建立起来,你只要负责C#与OPC完成通讯就可以了

回答3:

FX系列的串口 : ComFxPlc.DLL
网口:EntFxPlc.DLL
Q系列、L系列的串口 : ComQsPlc.DLL
网口:EntQsPlc.DLL

回答4:

http://bbs.gongkong.com/D/201704/710427_1.shtml

回答5:

PLC一般是485通讯,拿过来协议就好了